Most common electrical defects 2025 - Commercial/Industrial installations

Below is a list of the top 10 most common electrical work defects identified by TechSafe Australia during inspections of commercial/industrial installations in 2025.

The below defects represent about 49% of all defects identified on commercial/industrial installations in 2025.

Many of the defects are work quality issues that could easily be avoided without additional costs being incurred. Reducing these mistakes will mean fewer defect notices are issued, saving everyone time and money returning to properties to fix defects

Table 1 - Most common electrical defects 2025 - Commercial/Industrial - AS/NZS3000:2018

 Clause numberClause headingNon-compliance identified
12.10.7Fire protective measures

Cable entries into switchboards not adequately fire sealed.

To prevent the spread of fire, free space in excess of 5mm is required to be sealed by an acceptable fire-resistant sealer.

This includes open conduits entering the enclosure.

22.10.5.1Equipment identification

All equipment installed on a switchboard shall be legibly and indelibly identified in the English language.

Equipment shall be easily identified and correctly marked with a permanent label.

32.10.5.2Relationship of electrical equipment

Circuit breakers incorrectly marked at switchboard.

No marking at all or illegible labelling with a permanent marker or pen.

43.11.4.6Marking and recording of underground cable location

Underground cable routes not recorded at switchboard.

A site plan indicating the underground cable route is required to be located at the switchboard.

55.3.6.4Earth electrodes – Location

The location of the earthing electrode not identified at the main switchboard.

Earth electrodes must be identified at the main switchboard.

61.7.2Installation work practice

Installation components not adequately fixed in position.

Mostly relating to the adequate securing of individual items of electrical equipment such as heat pumps, switches etc.

72.3.2.2Devices for isolation

Isolation devices on equipment not labelled/incorrectly labelled.

No indication (unless obvious) of what equipment the isolator controls.

82.10.3.1Access to live parts

Live parts shall be arranged so that basic protection is provided by Enclosures.

Installations where live parts are accessible, Covers and doors are required to be fixed in position by a lock or screws, requiring a tool or key to enable access. 

Spare circuit breaker spaces to be fitted with pole fillers.

92.10.2.4Identification of main switchboards

The main switchboard shall be legibly and permanently marked “Main Switchboard”

104.5.1.1Location - Lighting equipment and accessories

All Lamp holders shall be located to be adequately protected against damage that might reasonably be expected in order to protect against inadvertent contact with live parts, low voltage lamp holders shall be located to minimise the risk of direct contact with live parts and mechanical damage.